Current Carrying Capacity Single Core Cables -BS 6004
CURRENT CARRYING CAPACITY: SINGLE CORE CABLES-COPPER CONDUCTORS TO BS 6004
CONDUCTOR | REFERENCE METHOD 4 | REFERENCE METHOD 3 | REFERENCE METHOD 1 | REFERENCE METHOD 11 | REFERENCE METHOD 12 (FREE AIR) | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|
CROSS SECTIONAL | enclosed in conduit in | enclosed in conduit on a | clipped direct | on a perforated cable tray | horizontal | vertical | |||||
AREA | thermally insulating wall etc | wall or in trunking etc | horizontal or vertical | flat spaced | spaced | trefoil | |||||
2 cables | 3 or 4 | 2 cables | 3 or 4 | 2 cables | 2 cables | 3 cable | |||||
2 cables | 3 or 4 | 2 cables | 3 or 4 | single phase | cables three | single phase | cables three | single phase | single phase | trefoil | |
single phase | cables three | single phase | cables three | a.c or d.c | phase a.c | a.c or d.c | phase a.c | a.c or d.c or 3 | a.c or d.c or 3 | three phase | |
a.c or d.c | phase a.c | a.c or d.c | phase a.c | flat touching | flat touching | flat touching | flat touching | cable tree phase | cable tree phase | a.c | |
or trefoil | or trefoil | ||||||||||
mm2 | A | A | A | A | A | A | A | A | A | A | A |
1 | 11 | 10.5 | 13.5 | 12 | 15.5 | 14 | - | - | - | - | - |
1.5 | 14.5 | 13.5 | 17.5 | 15.5 | 20 | 18 | - | - | - | - | - |
2.5 | 20 | 18 | 24 | 21 | 27 | 25 | - | - | - | - | - |
4 | 26 | 24 | 32 | 28 | 37 | 33 | - | - | - | - | - |
6 | 34 | 31 | 41 | 36 | 47 | 43 | - | - | - | - | - |
10 | 46 | 42 | 57 | 50 | 65 | 59 | - | - | - | - | - |
16 | 61 | 56 | 76 | 68 | 87 | 79 | - | - | - | - | - |
25 | 80 | 73 | 101 | 89 | 114 | 104 | 126 | 112 | 146 | 130 | 110 |
35 | 99 | 89 | 125 | 110 | 141 | 129 | 156 | 141 | 181 | 162 | 137 |
50 | 119 | 108 | 151 | 134 | 182 | 167 | 191 | 172 | 219 | 197 | 167 |
70 | 151 | 136 | 192 | 171 | 234 | 214 | 246 | 223 | 281 | 254 | 216 |
95 | 182 | 164 | 232 | 207 | 284 | 261 | 300 | 273 | 341 | 311 | 264 |
120 | 210 | 188 | 269 | 239 | 330 | 303 | 349 | 318 | 396 | 362 | 308 |
150 | 240 | 216 | 300 | 262 | 381 | 349 | 404 | 369 | 456 | 419 | 356 |
185 | 273 | 245 | 341 | 296 | 436 | 400 | 463 | 424 | 521 | 480 | 409 |
240 | 320 | 286 | 400 | 346 | 515 | 472 | 549 | 504 | 615 | 569 | 485 |
300 | 367 | 328 | 458 | 394 | 594 | 545 | 635 | 584 | 709 | 659 | 561 |
400 | - | - | 546 | 467 | 694 | 634 | 732 | 679 | 852 | 795 | 656 |
500 | - | - | 626 | 533 | 792 | 723 | 835 | 778 | 982 | 920 | 749 |
630 | - | - | 720 | 611 | 904 | 826 | 953 | 892 | 1138 | 1070 | 855 |
800 | - | - | - | - | 1030 | 943 | 1086 | 1020 | 1265 | 1188 | 971 |
1000 | - | - | - | - | 1154 | 1058 | 1216 | 1149 | 1420 | 1337 | 1079 |
REFERENCE METHODS OF INSTALLATION ARE DESCRIBED IN IEEE REGULATIONS & B.S. 7671